Impact of Converter-Interfaced Generation to the Frequency Response of the European Power System
2019
The increase of converter-interfaced generation (CIG) typically related to renewable energy sources is progressively causing a significant change of power systems operation. The curtailment of synchronous generation with the consequent reduction of the overall kinetic energy is one of the related issues, currently under investigation in academia and industry. The work considers the problem of overall inertia reduction from a large-scale point of view, analyzing the impact of different CIG integration levels to the frequency response of the power system of Continental Europe. The kinetic energy is evaluated for each country of the synchronous area, and the system is modified substituting con…
Impact of the high share of converter-interfaced generation on electromechanical oscillations in Continental Europe power system
2020
This study investigates the effects of converter-interfaced generation integration on the dynamic response of the power system of Continental Europe. The system is analysed with a large-scale dynamic model of the entire synchronous area, considering different instantaneous integration percentages of converter-interfaced generation across the system. The study focuses on the reduction of the overall available kinetic energy and the impact on frequency dynamics and system oscillations. The dynamic model of the system originally provided by ENTSO-E is further developed according to a specific methodology, replacing a determined amount of synchronous generation and introducing a corresponding a…